Power Transfer Switches

ASCO 7000 SERIES Service Entrance Transfer Switch

Our line of ASCO 7000 SERIES Service Entrance Power Transfer Switch combines automatic power switching with a disconnect and overcurrent protective device on the utility source. These are typically installed at facilities that have a single utility feed and a single emergency power source.​

Best Suited For
  • Education
  • Healthcare
  • Government
  • Manufacturing
  • Transportation
  • Power Generation
Limited Guardian Warranty
How to buy

Specifications

Specifications per model ASCO 7000 SERIES Service Entrance Transfer Switch
Ampere Size Pole Count Voltage Enclosure Type
70 - 4000A 2, 3, 4 115 - 600V Type 1, 3R, 3RX, 4, 4X, 12
* To view a specific model product page click on the model name above.

Features

Available from 150 to 4000 amperes
Disconnect and overcurrent protective device on the utility source: molded case circuit breaker 150 to 800 Amp; insulated case 1000 to 4000 Amp
Ground and neutral bus, all silver-plated copper
Solderless screw type terminals for External Power Connections
Labeled UL 891, Meets all NEC

Benefits

The ASCO 7000 SERIES Service Entrance Power Transfer Switch combines automatic power switching with a disconnect and overcurrent protective device on the utility source.
Uses the same reliable transfer switching mechanism and controller as the 7000 SERIES product platform.
Includes a utility circuit breaker as a disconnect device and links for connecting both neutral and ground conductors.

Services & Support

Support

Frequently Asked Questions
Q
Where can I send remote transfer signal?
A
The transfer switch has a feature connected to the field connections terminal block (TB) called Feature 17 or Remote Transfer to Emergency Feature. This requires a customer supplied normally open contact wherein closing of the contact causes engine start and transfer to the emergency source.
Q
How does the ATS work?
A
The ATS works like a conventional open transition transfer switch. The transfer switch main contacts moves in a quick break - before make mode transition. There is no momentary parallel connection of the two sources and no extended center-off position during transfer. The transition is quick. The ATS controller monitors the voltage and frequency of the two sources (upon re-transfer or any transfer between 2 “live” sources) and ensures that they are in-phase before the load is transferred (if enabled).
Q
How will I know if the controller is damaged?
A
The controller is damaged if the display doesn’t work; If there are extensive signs of burns on the PC board; If the OP and NR relays are no longer functional.
Q
Why won't the ATS transfer to Emergency?
A
The ATS won’t transfer to Emergency if: Emergency is unavailable; The Transfer to Emergency Inhibit is activated; The Load Shed from Emergency feature is activated; The solenoid operator is damaged; The ER relay is damaged; The controller is damaged; There is mechanical failure.
Q
Where do I connect the engine start wires?
A
The engine start contacts are also known as feature 7 and 8. Feature 7 is a contact that closes to send an engine start signal and Feature 8 is a contact that opens to send an engine start signal. Refer to the transfer switch wiring diagram for the terminal connections. To request for a wiring diagram just take note of the Serial no., BOM no. and the Catalog no. of the transfer switch and call 1-800-800-ASCO (2726) option 33.

Contacts

Sales In USA Change Location
ASCO Power Technologies (Maryland, Southern Delaware, Washington DC and VA)
Email Contact +1 571 313 8041 Fax +1 703 342 0391
12310 Pinecrest Road, Suite 204 Reston Virginia 20191 USA
Product areas of focus: Power Transfer Switches, Paralleling Switch Gear, Power Control and Monitoring
ASCO Power Technologies (Maryland, Southern Delaware, Washington DC and VA) Justin Mitros
Email Contact +1 571 313 8041 Fax +1 703 342 0391
12310 Pinecrest Road, Suite 204 Reston Virginia 20191 USA
Product areas of focus: Power Transfer Switches, Paralleling Switch Gear, Power Control and Monitoring
Support Change Location
ASCO Services, Inc.
50 Hanover Road Florham Park New Jersey 07932
Product areas of focus: Power Transfer Switches, Paralleling Switch Gear, Power Control and Monitoring

LATEST INDUSTRY TRENDS, TECHNOLOGIES AND SOLUTIONS

Availability & Uptime

ASCO 5170 Quad-Ethernet Module Accessory 72EE2

The 5170 Quad-Ethernet Module is the best way to remotely communicate to your ASCO Power Transfer Switches. Get real-time power monitoring, control and historical insight into the utility, generator and transfer switch on any smart phone,...

April 6, 2017
Data Center/Colocation/Hosting

Leveraging The Internet of Things in the Data Center and Edge

March 31, 2017
Availability & Uptime

ASCO 5370 Touch Display Interface (TDI)

The ASCO 5370 Touch Display Interface (TDI) is a premium user-friendly experience for accessing data quickly, optimizing reaction time and maximizing efficiency.

April 6, 2017
;